How to use this calculator
- Enter the set's rating in kWe and the load as a percentage of that rating.
- Enter the SFC at full load in L/kWh or g/kWh. If you have the manufacturer's fuel table, use it. Otherwise the default 0.24 L/kWh is a mid-range modern diesel value.
- Check the part-load multipliers. Replace them with ratios from the datasheet if available (SFC at each load ÷ SFC at full load).
- Add running hours per day, usable tank volume and fuel price for daily use, runtime and cost.
How it works: the formula
Specific fuel consumption is fuel used per unit of electrical energy produced. It is lowest near rated load and rises at part load, because friction, pumping and alternator losses stay roughly constant while output falls. Multiplying SFC by kW gives litres per hour directly.
Variables and units
| Symbol | Meaning | Unit |
|---|---|---|
| P_rated | Generator prime or continuous electrical rating | kWe |
| SFC | Specific fuel consumption at the given load | L/kWh or g/kWh |
| k(load) | Part-load multiplier: SFC at load ÷ SFC at 100 % | — |
| ρ | Diesel density (default 0.835) | kg/L |
| F | Volumetric fuel rate | L/h |
Worked example
A 100 kWe set at 75 % load, full-load SFC 0.24 L/kWh, default curve (k = 1.03 at 75 %), 8 h per day, 500 L usable tank, fuel at 1.20 per litre:
Using a datasheet value of 200 g/kWh at full load with ρ = 0.835 kg/L: SFC = 200 / 835 = 0.2395 L/kWh. A set at 100 kW then burns 23.95 L/h.
Assumptions
- Constant load over the period.
- The default part-load curve (25 %: 1.40, 50 %: 1.12, 75 %: 1.03, 100 %: 1.00) is a generic, deliberately conservative shape, not any maker's data.
- Below 25 % load the multiplier is extrapolated along the 25–50 % slope, and a warning is shown.
Limitations
- A manufacturer's fuel consumption table for your exact engine, rating and frequency is always better than a generic estimate.
- Real loads vary. For a load that changes during the day, work out each period separately and add the results.
- Fuel density varies with grade and temperature. Volume-based figures shift by a few percent.
- Engine condition, altitude, ambient temperature and fuel quality all affect consumption.
References
Standards and texts that cover this topic. Use the edition adopted in your jurisdiction.
- ISO 3046-1, Reciprocating internal combustion engines — Performance — Part 1: declarations of power, fuel and lubricating oil consumptions, and test methods.
- ISO 8528-1 — generating set ratings (prime, continuous, standby) used to define "rated kW".
- EN 590 and ASTM D975 — automotive and distillate diesel fuel specifications (density limits for EN 590 diesel are 0.820–0.845 kg/L at 15 °C).
Frequently asked questions
What SFC should I use if I have no datasheet?
Modern turbocharged diesel sets usually fall between 0.21 and 0.25 L/kWh (about 175–210 g/kWh) at 75–100 % load. Small sets sit at the higher end. The default 0.24 L/kWh is a cautious mid-range value. Treat any generic value as approximate.
Why does fuel per kWh increase at low load?
Part of the fuel goes into overcoming the engine's own friction and pumping losses, which barely change with load. At light load those fixed losses are a larger share of the output, so each kWh costs more fuel.
Is running a diesel generator at very low load harmful?
Long periods below roughly 30 % load can cause wet stacking: unburnt fuel and soot building up in the exhaust. Manufacturers usually state a minimum recommended load or require periodic load-bank runs.
How do I convert g/kWh to L/kWh?
Divide by density in g/L. At 0.835 kg/L (835 g/L), 200 g/kWh ÷ 835 = 0.2395 L/kWh. The calculator does this conversion and shows it in the working.
Related calculators
- Generator Sizing Calculator — Size a generator set from a load table: running kW/kVA, diversity, motor starting kVA by DOL, soft starter or VFD, margin, derating and a common kVA rating.
- kVA to kW Converter (and kVAr) — Convert between kVA, kW and kVAr using power factor, solve the power triangle from any two values and get the matching line current.
- Battery Runtime Calculator with Peukert — Estimate battery bank runtime from Ah, voltage, depth of discharge and inverter efficiency, with an optional Peukert correction and a series/parallel bank builder.
How these formulas were checked: methodology and testing.