How to use this calculator
- Select three-phase or single-phase. For three-phase, state whether the voltage you know is line-to-line (for example 400 V or 480 V) or line-to-neutral (230 V or 277 V).
- Choose the power unit. Use kW for real power, hp for a motor's rated shaft output, or kVA when you know the apparent power, as with transformers and generators.
- Enter the power factor. For kW and hp inputs also enter the efficiency: 1 when the figure is already electrical input, or the motor efficiency when it is shaft output.
- Read the current, then look at the working panel to see the formula with your values substituted.
- Copy the link to share the exact inputs, or print the result for a calculation file.
How it works: the formula
The √3 comes from the geometry of a balanced three-phase system. The voltage between two lines is √3 times the voltage from a line to neutral, and total power is three times the per-phase power: P = 3 × V_LN × I × PF = √3 × V_LL × I × PF. Rearranging that gives the current.
Variables and units
| Symbol | Meaning | Unit |
|---|---|---|
| I | Line current | A |
| P | Real (active) power: output power if η < 1, input power if η = 1 | W |
| S | Apparent power | VA |
| V_LL | Line-to-line voltage | V |
| V_LN | Line-to-neutral (phase) voltage | V |
| PF | Power factor, cos φ (0 < PF ≤ 1) | — |
| η | Efficiency, output ÷ input (0 < η ≤ 1) | — |
Worked example
A 100 kW three-phase load on a 400 V supply at power factor 0.8, with P taken as electrical input (η = 1):
For a 500 kVA transformer secondary at 415 V, the full-load current is 500 000 / (1.73205 × 415) = 695.60 A. If the same 100 kW load were described by its 230 V line-to-neutral voltage, V_LL = 1.73205 × 230 = 398.37 V and the current is 181.16 A. The small difference comes from 230 V × √3 being slightly less than 400 V.
Assumptions
- Three-phase loads are balanced, so every line carries the same current.
- Voltages and currents are sinusoidal. PF is the displacement power factor.
- When you enter hp, P is the motor's shaft output, converted at 1 hp = 745.7 W.
Limitations
- Real motor current at a given load depends on the motor's design. For protective devices and conductors, use the nameplate full-load current, or the motor current tables in your code (NEC Article 430 tables, for example) where they apply.
- Unbalanced three-phase loads need each phase worked out separately.
- Harmonic currents from electronic loads raise RMS current above this sinusoidal estimate.
- Starting (inrush) current is several times the running current and is not covered here.
References
Standards and texts that cover this topic. Use the edition adopted in your jurisdiction.
- IEEE Std 141, Recommended Practice for Electric Power Distribution for Industrial Plants ("Red Book") — power and current relationships in three-phase systems.
- IEC 60050-131 / IEC 60050-141, International Electrotechnical Vocabulary — definitions of active, reactive and apparent power and polyphase quantities.
- NFPA 70, National Electrical Code, Article 430 — motor full-load current tables used for conductor and protection sizing in NEC jurisdictions.
Frequently asked questions
Why does three-phase current use √3 rather than 3?
Total three-phase power is 3 × V_LN × I × PF. Because V_LL = √3 × V_LN, the same power written with line-to-line voltage is √3 × V_LL × I × PF. With line-to-line voltage the factor is √3; with line-to-neutral voltage it is 3. This calculator converts for you when you choose line-to-neutral.
Should I use efficiency for a motor?
Yes, when the power you have is the rated shaft output, which is what a nameplate kW or hp figure normally is. The motor takes more electrical power than it delivers, so divide by efficiency. If you measured electrical input power with a meter, leave efficiency at 1.
Why does the kVA input ignore power factor?
Apparent power already includes the effect of power factor: S = V × I for single-phase and √3 × V_LL × I for three-phase. Power factor only matters when you start from real power. Here it is used only to split the kVA into kW and kVAr.
Is 400 V the same as 230 V three-phase?
On a 230/400 V system, 230 V is the line-to-neutral voltage and 400 V is the line-to-line voltage of the same supply. Pick the selector that matches the number you enter. Getting this wrong changes the current by a factor of √3.
Can I use this to choose a breaker size?
Only as a starting point. Breaker and conductor sizing must follow your installation code. That means continuous-load factors, motor rules, grouping and ambient corrections, and the manufacturer's data.
Related calculators
- kVA to kW Converter (and kVAr) — Convert between kVA, kW and kVAr using power factor, solve the power triangle from any two values and get the matching line current.
- Cable Voltage Drop Calculator — Voltage drop for single-phase, three-phase and DC cables with temperature-corrected copper or aluminium resistance, reactance, % limit check and minimum size solver.
- Generator Sizing Calculator — Size a generator set from a load table: running kW/kVA, diversity, motor starting kVA by DOL, soft starter or VFD, margin, derating and a common kVA rating.
How these formulas were checked: methodology and testing.