How the values are calculated
The equal-resistance column takes the smallest standard IEC size of aluminium whose resistance does not exceed that of the copper conductor. Because standard sizes come in steps, that is the first standard size above 1.64 × the copper size, which is often two sizes up: 16 mm² copper needs 35 mm² aluminium on resistance alone. An aluminium conductor of exactly equal resistance weighs about 50 % of the copper one.
Voltage drop on the same run
Three-phase 400 V, 150 A at power factor 0.85, 120 m route, conductor at 70 °C, reactance 0.08 mΩ/m for all three cables:
| Conductor | R at 70 °C (mΩ/m) | Voltage drop (V) | Voltage drop (%) |
|---|---|---|---|
| Copper 70 mm² | 0.2947 | 9.12 | 2.28 |
| Aluminium 70 mm² | 0.4851 | 14.2 | 3.54 |
| Aluminium 120 mm² | 0.283 | 8.81 | 2.2 |
Swapping copper for aluminium of the same size raises the drop from 2.28 % to 3.54 %; moving up to 120 mm² aluminium brings it back to 2.2 %. Current-carrying capacity must still be checked separately, because aluminium tables differ from the copper ones.
IEC 60228 and real conductor resistance
IEC 60228 defines conductor classes (solid, stranded, flexible) and the maximum DC resistance at 20 °C for each size of copper and aluminium conductor. Those maxima are close to, but not identical with, the resistivity values used here, because stranding and manufacturing tolerances are built in. For a final design use the IEC 60228 table or the cable maker's data, which the voltage drop calculator accepts as a resistance input.