Runtime of a 48 V LiFePO4 Battery Bank
Lithium iron phosphate (LiFePO4) batteries are now common in solar and backup systems because they tolerate deeper discharge and more cycles than lead-acid. A "48 V" bank is usually built from cells or modules with a nominal 3.2 V per cell, so four 12.8 V modules in series give 51.2 V nominal.
The calculator below is preset for four 12.8 V 100 Ah modules in series, 80 % usable depth of discharge, a 1000 W AC load and 92 % inverter efficiency. The result shows the bank energy, the battery current and the runtime; adjust the depth of discharge to the limit your battery management system and warranty allow.
Last reviewed
For estimation and education. Not a substitute for a licensed engineer, the applicable codes (IEC 60364, NEC/NFPA 70, BS 7671, local regulations) or manufacturer data. Read the disclaimer.
Result
Battery runtime — Engineerly. Estimate for education only; verify against applicable codes and manufacturer data.
- Runtime
- 3.77h
- Runtime
- 226min
- Bank
- 51.2 V, 100 Ah
- Bank energy (nominal)
- 5.12kWh
- Usable energy at DoD
- 4.096kWh
- Battery current
- 21.23A
- C-rate
- 0.212C
Working, with your numbers
- 1. Bank voltage (series adds volts)V = V_unit × N_sV = 12.8 V × 4= 51.2 V
- 2. Bank capacity (parallel adds Ah)C = Ah_unit × N_pC = 100 Ah × 1= 100 Ah
- 3. Battery currentI = P_load / (V × η)I = 1,000 W / (51.2 V × 0.92)= 21.23 A
- 4. Runtime (ideal capacity)t = C × V × DoD × η / Pt = 100 Ah × 51.2 V × 0.8 × 0.92 / 1,000 W= 3.768 h
Assumptions
- Constant power load for the whole discharge; battery voltage taken as the nominal bank voltage.
- Usable depth of discharge 80 % of rated capacity.
- Inverter efficiency 92 %, constant over the load range.
- All units in the bank are identical, healthy and balanced.
Check before you rely on this
- Capacity also falls at low temperature and with ageing; many designers add an ageing factor (for example 1.25 in IEEE 485 for lead-acid).
- Estimation and education only. Not a substitute for a licensed engineer, the applicable code (IEC 60364, NEC/NFPA 70, BS 7671 or local regulations) or manufacturer data.
Notes for this case
- LiFePO4 has a Peukert exponent close to 1, so the simple energy method is usually adequate.
- The battery management system may cut off before the nominal depth of discharge at low temperature or high current.
- Usable capacity declines with age; many designers add a margin for end-of-life capacity.
Open the full calculator page with the formula, worked example and references
Related calculators
- Solar PV sizingSize an off-grid solar PV system: array kWp and panel count from daily energy and peak sun hours, battery Ah for days of autonomy, and charge controller current.
- Generator fuel useEstimate diesel generator fuel use in L/h from load and specific fuel consumption with an editable part-load curve, plus daily use, tank runtime and cost.
- Voltage dropVoltage drop for single-phase, three-phase and DC cables with temperature-corrected copper or aluminium resistance, reactance, % limit check and minimum size solver.
Embed this calculator
Paste this code into your page to show the calculator in a frame. The attribution link must stay visible. The embedded page carries no ads and stores nothing.
How these formulas were checked: methodology and testing.