Cable Size for a 100 A Three-Phase Submain (XLPE, Clipped Direct)

A submain from the main switchboard to a floor or building distribution board is a typical case where both checks matter: the cable must carry the design current at the site's ambient temperature, and the route is often long enough that voltage drop decides the size.

The calculator below is preset for a three-phase 400 V copper XLPE cable, three loaded conductors, installed by method C (clipped direct to a wall) as a single circuit, 100 A design current, 40 °C ambient, 80 m route, power factor 0.9 and a 3 % voltage drop limit. It reports the size needed for current-carrying capacity, the size needed for voltage drop and the larger of the two.

Last reviewed

Heat from the conductor must escape through the insulation into the surroundings. A hotter ambient or grouped neighbours slow that, so the tabulated capacity is multiplied by correction factors: Iz = I₀ · ka · kg.

For estimation and education. Not a substitute for a licensed engineer, the applicable codes (IEC 60364, NEC/NFPA 70, BS 7671, local regulations) or manufacturer data. Read the disclaimer.

Inputs

Capacity source

Cable

Insulation
Loaded conductors

Copper only. Source: IEC 60364-5-52 Table B.52.5.

Load and protection

A
A

When entered, the cable is sized so that Iz ≥ In

Correction factors

°C

Fills Ca from Ca = √((θmax − θa)/(θmax − 30))

IEC 60364-5-52 Table B.52.14, typical values: 25 °C 1.04 · 30 °C 1.00 · 35 °C 0.96 · 40 °C 0.91 · 45 °C 0.87 · 50 °C 0.82

Grouping arrangement

Circuits or multi-core cables grouped together (1 to 9)

IEC 60364-5-52 Table B.52.17 (circuits: factor): 1: 1.00 · 2: 0.85 · 3: 0.79 · 4: 0.75 · 5: 0.73 · 6: 0.72 · 7: 0.72 · 8: 0.71 · 9: 0.70

Voltage-drop check

System
V
m
Length unit
mΩ/m

Default 0.08 mΩ/m

%

Conductor taken at 90 °C for the voltage drop

Notes for this case

  • Reference capacities are copper values from IEC 60364-5-52 Table B.52.5 (XLPE, three loaded conductors), method C.
  • The protective device rating must satisfy Ib ≤ In ≤ Iz; check it with the breaker sizing calculator.
  • Cables in trays, ducts or ground use other installation methods and factors that are not built in.

Open the full calculator page with the formula, worked example and references