Cable Size for a 100 A Three-Phase Submain (XLPE, Clipped Direct)
A submain from the main switchboard to a floor or building distribution board is a typical case where both checks matter: the cable must carry the design current at the site's ambient temperature, and the route is often long enough that voltage drop decides the size.
The calculator below is preset for a three-phase 400 V copper XLPE cable, three loaded conductors, installed by method C (clipped direct to a wall) as a single circuit, 100 A design current, 40 °C ambient, 80 m route, power factor 0.9 and a 3 % voltage drop limit. It reports the size needed for current-carrying capacity, the size needed for voltage drop and the larger of the two.
Last reviewed
For estimation and education. Not a substitute for a licensed engineer, the applicable codes (IEC 60364, NEC/NFPA 70, BS 7671, local regulations) or manufacturer data. Read the disclaimer.
Result
Cable size by current-carrying capacity — Engineerly. Estimate for education only; verify against applicable codes and manufacturer data.
- Recommended size
- 25mm²
- Iz of the recommended size
- 115.6A
25 mm²: current-carrying capacity and voltage drop give the same size.
- Required reference capacity It
- 109.89A
- Size by current-carrying capacity
- 25 mm² (It 127 A, Iz 115.6 A)
- Size by voltage drop (3 %)
- 25 mm²
- Voltage drop at the recommended size
- 11.45 V (2.86 %)
- Source table
- IEC 60364-5-52 Table B.52.5
Reference capacities used: IEC 60364-5-52 Table B.52.5, method C
Copper conductors, ambient air 30 °C. Iz = It × Ca × Cg with your factors.
| mm² | It (A) | Iz (A) |
|---|---|---|
| 1.5 | 23 | 20.93 |
| 2.5 | 31 | 28.21 |
| 4 | 42 | 38.22 |
| 6 | 54 | 49.14 |
| 10 | 75 | 68.25 |
| 16 | 100 | 91 |
| 25 | 127 | 115.6 |
| 35 | 158 | 143.8 |
| 50 | 192 | 174.7 |
| 70 | 246 | 223.9 |
| 95 | 298 | 271.2 |
| 120 | 346 | 314.9 |
| 150 | 399 | 363.1 |
| 185 | 456 | 415 |
| 240 | 538 | 489.6 |
Working, with your numbers
- 1. Required reference capacityIt ≥ Ib / (Ca × Cg)It ≥ 100 A / (0.91 × 1)= 109.89 A
- 2. Smallest tabulated size meeting ItIt(S) ≥ It,requiredIt(25 mm²) = 127 A ≥ 109.89 A= 25 mm²
- 3. Current-carrying capacity after correctionIz = It × Ca × CgIz = 127 A × 0.91 × 1= 115.57 A
- 4. Resistance at conductor temperatureR_T = ρ20 (1 + α (T − 20)) / AR_T = 0.017241 × (1 + 0.00393 × (90 − 20)) / 25 mm²= 0.87936 mΩ/m
- 5. Voltage drop (three-phase, line-to-line)ΔV = √3 × I × L × (R cosφ + X sinφ) / nΔV = 1.73205 × 100 A × 80 m × (0.00087936 × 0.9 + 8.00000e-5 × 0.4359) Ω/m / 1= 11.45 V
- 6. Percentage of nominal voltageΔV% = ΔV / V × 100ΔV% = 11.4495 V / 400 V × 100= 2.86 %
Assumptions
- Copper conductors; reference capacities from IEC 60364-5-52 Table B.52.5, method C, 3 loaded conductors, ambient air 30 °C.
- Ca = 0.91 and Cg = 1 as entered; Ca × Cg = 0.91.
- Voltage drop with one conductor per phase at 90 °C, resistance from resistivity (IEC sizes up to 630 mm²).
- Recommended size = the larger of the current-carrying-capacity size and the voltage-drop size.
Check before you rely on this
- Estimate only. The cable must also meet fault protection (automatic disconnection, IEC 60364-4-41) and short-circuit withstand k²S² ≥ I²t (IEC 60364-4-43).
- Harmonic currents (for example from LED drivers, IT equipment and drives) can load the neutral; IEC 60364-5-52 Annex E then reduces the capacity or sizes on the neutral current.
- Buried cables, ducts in the ground, trays, ladders and the other installation methods are not covered here; take their values and factors from IEC 60364-5-52 or the cable maker.
- Estimation and education only. Not a substitute for a licensed engineer, the applicable code (IEC 60364, NEC/NFPA 70, BS 7671 or local regulations) or manufacturer data.
Notes for this case
- Reference capacities are copper values from IEC 60364-5-52 Table B.52.5 (XLPE, three loaded conductors), method C.
- The protective device rating must satisfy Ib ≤ In ≤ Iz; check it with the breaker sizing calculator.
- Cables in trays, ducts or ground use other installation methods and factors that are not built in.
Open the full calculator page with the formula, worked example and references
Related calculators
- Voltage dropVoltage drop for single-phase, three-phase and DC cables with temperature-corrected copper or aluminium resistance, reactance, % limit check and minimum size solver.
- Breaker sizingPick a standard MCB or MCCB rating that satisfies Ib ≤ In ≤ Iz and the 1.45 Iz overload rule, with guidance on B, C and D trip curves for the load type.
- Short-circuit currentEstimate the three-phase prospective short-circuit current at a transformer's secondary from kVA, voltage and impedance %, and at the end of a cable run.