How Many Lights for an Office at 500 Lux
Offices are commonly designed around 500 lx on the working plane for desk tasks, which is the figure given for writing, typing and reading in the European lighting standard EN 12464-1. The lumen method turns that target into a number of luminaires once you know the room size, the luminaire output and two factors that account for room geometry and ageing.
The calculator below is preset for a 12 × 8 m open office with the luminaires 2.05 m above the desk height (a 2.8 m ceiling and 0.75 m desks), 3600 lm LED panels of 30 W, a utilisation factor of 0.6 and a maintenance factor of 0.8. Replace the utilisation factor with the value from the luminaire maker's table for your room index and reflectances.
Last reviewed
For estimation and education. Not a substitute for a licensed engineer, the applicable codes (IEC 60364, NEC/NFPA 70, BS 7671, local regulations) or manufacturer data. Read the disclaimer.
Result
Lighting (lumen method) — Engineerly. Estimate for education only; verify against applicable codes and manufacturer data.
- Luminaires needed
- 28
- Maintained illuminance achieved
- 504lx
28 luminaires give 504 lx, meeting the 500 lx target.
- Room area
- 96m²
- Room index K
- 2.34
- Exact number before rounding
- 27.778
- Suggested layout (rows × columns)
- 4 × 7 = 28
- Spacing along the length × across the width
- 1.71 m × 2 m
- Installed lighting power (layout)
- 840W
- Lighting power density
- 8.75W/m²
Working, with your numbers
- 1. Room areaA = L × WA = 12 m × 8 m= 96 m²
- 2. Room indexK = L × W / (Hm × (L + W))K = 96 / (2.05 × (12 + 8))= 2.341
- 3. Number of luminaires (exact)N = E × A / (Φ × n × UF × MF)N = 500 lx × 96 m² / (3,600 lm × 1 × 0.6 × 0.8)= 27.778
- 4. Number of luminaires (rounded up)N = ⌈N_exact⌉N = ⌈27.7778⌉= 28
- 5. Maintained illuminance with the rounded numberE = N × Φ × n × UF × MF / AE = 28 × 3,600 × 1 × 0.6 × 0.8 / 96= 504 lx
- 6. Suggested layoutrows × columns ≥ N, columns along the length4 × 7= 28
- 7. Installed lighting powerP = N_layout × P_luminaireP = 28 × 30 W= 840 W
- 8. Lighting power densityLPD = P / ALPD = 840 W / 96 m²= 8.75 W/m²
Assumptions
- Lumen method: average maintained illuminance on the working plane over the whole room area.
- Utilisation factor 0.6 and maintenance factor 0.8 as entered.
- Mounting height is measured from the working plane to the luminaires, not from the floor.
- Columns run along the room length and rows across the width; the first and last luminaires sit half a spacing from the walls.
Check before you rely on this
- The utilisation factor depends on the luminaire's light distribution, the room index and the ceiling, wall and floor reflectances. Take it from the maker's UF table for your luminaire; 0.6 is only an example.
- The lumen method gives the average illuminance on the working plane. Uniformity, glare (UGR), cylindrical illuminance and emergency lighting need a point-by-point calculation, for example in DIALux or Relux.
- Keep the luminaire spacing within the maximum spacing-to-height ratio given by the maker, or the light will be uneven.
- Estimation and education only. Not a substitute for a licensed engineer, the applicable code (IEC 60364, NEC/NFPA 70, BS 7671 or local regulations) or manufacturer data.
Notes for this case
- The lumen method gives the average illuminance; uniformity and glare need a point-by-point calculation in lighting design software.
- Arrange luminaires so the spacing does not exceed the maker's maximum spacing-to-height ratio.
- Daylight and controls reduce energy use but do not change the installed number needed for night-time.
Open the full calculator page with the formula, worked example and references
Related calculators
- Electricity costList your appliances with watts, quantity, hours per day and days per month to get kWh and cost per month and per year at your own tariff, in any currency.
- Breaker sizingPick a standard MCB or MCCB rating that satisfies Ib ≤ In ≤ Iz and the 1.45 Iz overload rule, with guidance on B, C and D trip curves for the load type.
- Cable size (ampacity)Choose a copper cable size from IEC 60364-5-52 reference current-carrying capacities with ambient temperature and grouping factors, then check voltage drop and take the larger size.