Voltage Drop in 12 V and 24 V DC Solar and Battery Cables
At 12 V or 24 V the same power needs ten to twenty times the current of a 230 V circuit, so a cable that would be generous on mains can lose several percent of the voltage in a few metres. In a battery system that lost voltage is lost energy and can make an inverter trip on low voltage while the battery is still well charged.
The calculator below is preset for a 24 V circuit carrying 40 A over a 6 m one-way route in 16 mm² copper at a conductor temperature of 50 °C, a typical battery-to-inverter or controller-to-battery link. Change the current, length and size to your own run; the result shows the drop in volts and percent and the smallest size that keeps within the limit.
Last reviewed
For estimation and education. Not a substitute for a licensed engineer, the applicable codes (IEC 60364, NEC/NFPA 70, BS 7671, local regulations) or manufacturer data. Read the disclaimer.
Result
Voltage drop — Engineerly. Estimate for education only; verify against applicable codes and manufacturer data.
- Voltage drop
- 0.5782V
- Voltage drop
- 2.41%
Within your 3 % limit.
- Voltage at load end
- 23.422V
- Conductor resistance at temperature
- 1.205mΩ/m
- Route length (one way)
- 6 m
- Smallest IEC size meeting 3 %
- 16 mm² (2.41 %)
Working, with your numbers
- 1. Resistance at conductor temperatureR_T = ρ20 (1 + α (T − 20)) / AR_T = 0.017241 × (1 + 0.00393 × (50 − 20)) / 16 mm²= 1.2046 mΩ/m
- 2. Voltage drop (DC, out and back)ΔV = 2 × I × L × R / nΔV = 2 × 40 A × 6 m × 0.00120461 Ω/m / 1= 0.5782 V
- 3. Percentage of nominal voltageΔV% = ΔV / V × 100ΔV% = 0.578211 V / 24 V × 100= 2.41 %
Assumptions
- Copper ρ20 = 0.017241 Ω·mm²/m, α = 0.00393 /K, conductor at 50 °C.
- Resistance from resistivity and nominal area (DC resistance; slightly below tabulated maximum values for stranded conductors).
- DC two-wire circuit: out and back, no reactance.
- Load current is constant along the route (a single load at the far end).
- The approximate formula ΔV = k·I·L·(R cos φ + X sin φ) is accurate for drops of a few percent.
Check before you rely on this
- Voltage drop is only one check. The conductor must also carry the current (IEC 60364-5-52 / NEC 310.16 ampacity with grouping and ambient corrections) and satisfy fault-disconnection and short-circuit withstand requirements.
- Estimation and education only. Not a substitute for a licensed engineer, the applicable code (IEC 60364, NEC/NFPA 70, BS 7671 or local regulations) or manufacturer data.
Notes for this case
- DC drop is computed out and back (factor 2) with no reactance.
- Many installers aim for 1–3 % on DC battery and PV cables; follow your inverter and controller manuals, which often state a maximum cable length per size.
- Ampacity and fusing still apply: a battery cable must be protected by a DC-rated fuse or breaker close to the battery.
Open the full calculator page with the formula, worked example and references
Related calculators
- Line currentCalculate line current from kW, hp or kVA for three-phase (line-to-line or line-to-neutral) and single-phase supplies, with PF, efficiency and every step shown.
- Transformer loadingFind transformer percentage loading, full-load currents on both windings, copper loss scaled with load squared, total losses and efficiency at the actual load.
- Solar PV sizingSize an off-grid solar PV system: array kWp and panel count from daily energy and peak sun hours, battery Ah for days of autonomy, and charge controller current.
Embed this calculator
Paste this code into your page to show the calculator in a frame. The attribution link must stay visible. The embedded page carries no ads and stores nothing.
How these formulas were checked: methodology and testing.