Skip to content
Engineerly

1000 kVA Diesel Generator Fuel Consumption (L/h at 25–100 % Load)

A 1000 kVA generator set is rated 800 kW at the conventional power factor of 0.8. On the generic part-load curve used across this site it burns about 67.2 L/h at a quarter load and 192 L/h at full load, so a full day at 75 % load needs roughly 3,560 litres.

A 1000 kVA set belongs to the class used for large industrial sites, hospitals, data centres and utility supplies. Sets of this size are often synchronised in parallel and may feed a medium-voltage network through a step-up transformer.

Last reviewed

Fuel use of a 1000 kVA set by load

Worked example at 75 % load

The set delivers 75 % of its 800 kW rating. The part-load multiplier at 75 % is 1.03, so each kWh costs slightly more fuel than at full load.

P = 1000 kVA × 0.8 × 0.75 = 600 kW SFC = 0.24 L/kWh × 1.03 = 0.2472 L/kWh F = 600 kW × 0.2472 L/kWh = 148.3 L/h F = 148.3 / 3.785411784 = 39.18 US gal/h 24 h: 148.3 × 24 = 3,560 L Tank: 2000 L / 148.3 L/h = 13.5 h

Curve and assumptions

  • Full-load specific fuel consumption of 0.24 L/kWh (about 200 g/kWh at 0.835 kg/L), a value within the range quoted for modern diesel sets. It is not taken from any manufacturer's datasheet.
  • Generic part-load multipliers 1.4 at 25 %, 1.12 at 50 %, 1.03 at 75 %, 1 at 100 %. At 25 % load the set uses about 40 % more fuel per kWh than at full load.
  • Load in kW at a power factor of 0.8, the rating basis of ISO 8528-1. A load at a better power factor draws more kW from the same kVA and burns more fuel.
  • A steady load for the whole period, with no warm-up or idling time.

What changes the numbers

  • The engine itself: two sets of the same kVA from different makers, or of different ages, can differ noticeably. The datasheet consumption at 25, 50, 75 and 100 % load is the figure to use once the model is known.
  • A varying load: average the consumption over the hours spent at each load level rather than using the average load in one step, because the curve is not linear.
  • Site and condition: altitude, hot intake air, clogged filters, injector wear and low coolant temperature at light load all raise consumption.
  • Fuel itself: diesel density changes with temperature and grade, so the same mass of fuel occupies a slightly different volume.

Run your own numbers

The calculator opens preset to 800 kW at 75 % load. Enter your datasheet consumption, your own curve, hours per day, tank size and fuel price.

Diesel Generator Fuel Consumption Calculator