Standard Circuit Breaker Ratings (MCB and MCCB)

Circuit breakers are made in a series of standard rated currents, so a design never uses the exact design current: it takes the next standard rating that still protects the cable. This page lists the preferred MCB ratings of IEC 60898-1 with the instantaneous trip bands of the B, C and D curves, and the MCCB ratings commonly offered by manufacturers.

For each MCB rating the table also gives the conventional tripping current I2 = 1.45 × In, which IEC 60364-4-43 compares with 1.45 × Iz of the cable.

Last reviewed

MCB ratings and trip bands (IEC 60898-1)

Common MCCB rated currents

IEC 60947-2 does not fix a list of MCCB ratings. These values are widely offered across manufacturers' frame sizes, often with adjustable thermal and magnetic settings; check the range of the actual product.

  • 16 A
  • 20 A
  • 25 A
  • 32 A
  • 40 A
  • 50 A
  • 63 A
  • 80 A
  • 100 A
  • 125 A
  • 160 A
  • 200 A
  • 250 A
  • 320 A
  • 400 A
  • 500 A
  • 630 A
  • 800 A
  • 1000 A
  • 1250 A
  • 1600 A

How the values are calculated

Ib ≤ In ≤ Iz I2 ≤ 1.45 × Iz (MCB to IEC 60898-1: I2 = 1.45 × In) Type B: 3 × In < Im ≤ 5 × In Type C: 5 × In < Im ≤ 10 × In Type D: 10 × In < Im ≤ 20 × In

Worked example

A circuit with design current Ib = 28 A on a cable rated Iz = 36 A. The smallest standard MCB not below 28 A is 32 A, and 28 ≤ 32 ≤ 36 holds.

I2 = 1.45 × 32 = 46.4 A 1.45 × Iz = 1.45 × 36 = 52.2 A 46.4 A ≤ 52.2 A ✓ Type C band: 160 – 320 A

With a type C device, the earth-fault or short-circuit current at the far end of the circuit must reach at least 320 A (the top of the band) for the breaker to be sure of tripping instantaneously.

Notes and limits

  • The MCB list is the series of preferred values in IEC 60898-1 up to 125 A; manufacturers also make some intermediate and smaller ratings.
  • Type B suits resistive loads and long circuits, type C general and motor circuits, type D high-inrush loads such as transformers; a D curve on a long cable may not reach its instantaneous band.
  • The rated current says nothing about breaking capacity. Icn (IEC 60898-1) or Icu and Ics (IEC 60947-2) must be at least the prospective short-circuit current where the device is installed.