kVA to Amps Chart (230, 400, 415 and 480 V)

Full-load current is the first number needed to choose a cable, a breaker or a busbar for a generator, transformer or UPS rated in kVA. Because kVA is apparent power, the current follows from the voltage alone, without the power factor: I = S / (√3 × V) on a three-phase supply and I = S / V on single-phase.

The chart covers 31 common ratings from 5 to 2500 kVA at 230 V single-phase and at 400, 415 and 480 V three-phase (line-to-line). Every value is computed from the formula, not copied from a catalogue, and rounded to four significant figures.

Last reviewed

Full-load current by kVA rating

How the values are calculated

Three-phase: I = S × 1000 / (√3 × V_LL) Single-phase: I = S × 1000 / V S in kVA, V in volts, I in amperes, √3 = 1.73205

The three-phase values assume a balanced load and use the line-to-line voltage. The single-phase column uses the voltage across the load, here 230 V. Power factor does not enter, because a kVA rating already includes it; to start from kW, divide by the power factor first (kVA = kW / PF).

Worked example

A 500 kVA transformer or generator on a 400 V three-phase system:

I = 500 × 1000 / (1.73205 × 400) I = 500 000 / 692.82 = 721.7 A

At 415 V the same rating carries 695.6 A: the current falls in the ratio 400 / 415 because the same power is delivered at a higher voltage. A 10 kVA single-phase unit at 230 V carries 10 000 / 230 = 43.48 A.

Notes and limits

  • These are currents at rated output. The current in service depends on the actual load; use the transformer loading or line current calculator for a measured or planned load.
  • Large ratings are normally three-phase. The single-phase figures for the bigger sizes are shown only because the arithmetic is the same.
  • For motors, the kVA drawn depends on efficiency and power factor, so read the nameplate current or use the motor current converter instead of this chart.
  • Harmonic currents from electronic loads add to the RMS current; cables and transformers feeding such loads may need a margin beyond these values.

Full-load current by transformer size

Each page adds 433 V and the 6.6, 11 and 33 kV primary currents, a worked example and the uses of the figure.

Calculate your own case

The calculator takes your exact values, shows every step and keeps the inputs in the link so the result can be shared.

kVA to kW Converter (and kVAr)